Machine Model: CSVGN5
Following checks and corrections are applied during Validation and AutoCorrection.
- If 0 < Ts3 < Mult*TimeStep then Ts3 = Mult*TimeStep
- If 0.0 < Ts1 < 0.5*Mult*TimeStep then Tf = 0, ElseIf 0.5*Mult*TimeStep < Tf < Mult*TimeStep then Tf = Mult*TimeStep
- If 0.0 < Ts5 < 0.5*Mult*TimeStep then Ts5 = 0, ElseIf 0.5*Mult*TimeStep < Ts5 < Mult*TimeStep then Ts5 = Mult*TimeStep
- If 0.0 < Ts6 < 0.5*Mult*TimeStep then Ts6 = 0, ElseIf 0.5*Mult*TimeStep < Ts6 < Mult*TimeStep then Ts6 = Mult*TimeStep
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Model Equations and/or Block Diagrams
Parameters:
| Ts1 | Time constant, sec |
| Vemax | Vemax, pu |
| Ts2 | Lead time constant, sec |
| Ts3 | Lag time constant, sec |
| Ts4 | Lead time constant, sec |
| Ts5 | Lag time constant, sec |
| Ksvs | Gain, pu |
| Ksd | Gain, pu |
| Bmax | Bmax, pu |
| Bpmax | Bpmax, pu |
| Bpmin | Bpmin, pu |
| Bmin | Bmin, pu |
| Ts6 | Time constant, sec |
| DV | DV |